Authentic Motor thermal magnetic circuit breaker button 3P GV2ME20C motor protection switch setting current range 13-18A 100KA

USD 26.50USD 28.50

Authentic Motor thermal magnetic circuit breaker button 3P GV2ME20C motor protection switch setting current range 13-18A 100KA

Description
  • Dimensions

     
  • circuit diagram

     
  • Performance curve

main information
Product Series
TeSys
product name
GV2
Product short name
GV2ME
product type
breaker
Applications
Motor protection
Pole number
3P
Additional information
Network Type
AC
Network frequency
50/60 Hz conforming to IEC 60947-2
Control type
(Push type) button
Installation method
Rail mounting
Installation location
Vertical and
horizontal
Motor power (kW)
9 kW at 440 V AC 50/60 Hz
9 kW at 415 V
7.5 kW at 400 V
4 kW at 230 V
Rated current [In]
18 A
Type of release
Thermomagnetic
Electromagnetic tripping current
223 A
Thermal overload protection setting range
13… 18 A
Isolation function
Applicable to IEC 60947-1 § 7-1-6
Mechanical shock resistance
0.5 J IK04
Phase loss sensitivity
Complies with IEC 60947-4-1 § 7-2-1-5-2
Use category
AC-3 conforms to IEC 60947-4-1
AC category conforms to IEC 60947-2
Rated working voltage [Ue]
690 V AC 50/60 Hz conforming to IEC 60947-2
Rated insulation voltage [Ui]
600 V AC 50/60 Hz conforming to UL 508
690 V AC 50/60 Hz conforming to IEC 60947-2
600 V AC 50/60 Hz conforming to CSA C22.2 No 14
Rated impulse withstand voltage [Uimp]
6 kV conforming to IEC 947-2
Power consumption per pole
2.5 W
Mechanical life
100000 times
Electrical life
100000 cycles of AC-3 at 440 V In
100000 cycles of AC-3 at 440 V In / 2
Maximum conversions
25 cyc / h
specified load
Continuous compliance with IEC 60947-4-1
Wiring capacity
Power circuit: screw-in terminal 2 1… 6 mm² Cable selection: single-strand hard wire without wire terminal
Power circuit: screw-in terminal 2 1.5… 6 mm² cable selection: flexible wire without wire terminal
Power supply circuit: Screw-in terminal 2 1… 4 mm² Cable selection: flexible cord with wire terminal
Tightening torque
1.7 Nm screw-in terminal cable 1… 4 mm²
1.7 Nm screw-in terminal cable 1… 6 mm²
1.7 Nm screw-in terminal cable 1.5… 6 mm²
Breaking capacity
Icu:> = 100 kA at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
Icu: 3 kA at 690 V AC 50/60 Hz conforming to IEC 60947-2
Icu: 15 kA at 400 / 415 V AC 50/60 Hz according to IEC 60947-2
Icu: 8 kA at 440 V AC 50/60 Hz according to IEC 60947-2
Icu: 6 kA at 500 V AC 50/60 Hz according to IEC 60947- 2
Rated short-circuit breaking capacity [Ics]
75% at 690 V AC 50/60 Hz conforming to IEC 60947-2
50% at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
50% at 440 V AC 50/60 Hz conforming to IEC 60947-2
75% at 500 V AC 50/60 Hz conforming to IEC 60947-2
height
89 mm
width
44.5 mm
depth
78.2 mm
product weight
0.26 kg
surroundings
Standards compliant
IEC 60947-4-1
GB 14048.4
IEC 60947-1
IEC 60947-2
certified product
CCC
CE
Protective measures
TH
IP protection level
IP20 conforms to IEC 60529 (main body)
Shock and vibration resistance
Shock resistance 11 ms (30 gn) according to IEC 60068-2-27
Shock resistance (5 gn (5 ... 150 Hz)) according to IEC 60068-2-6
Ambient temperature
-20… 40 ° C inside the cabinet
-20… 60 ° C body
Storage temperature
-40… 80 ° C
Fire resistance and abnormal high temperature resistance
960 ° C conforming to IEC 60695-2-1
Working altitude
<= 2000 m
 
Specification

Rated voltage : 400/415VAC

is_customized : Yes

Type : Moulded Case

Model Number : GV2-ME20C 13-18A

Control type : Push button control

+